Temperature control is the single most important weapon against legionella bacteria in water systems. Get the temperatures right, and you dramatically reduce the risk. Get them wrong, and you create ideal breeding conditions for dangerous bacteria.
This guide explains exactly what temperatures you need to maintain, how to monitor them, where to take readings, how to record them, and what to do when things go wrong.
Do you monitor water temperatures regularly?
Let's see if your current approach is adequate.
Why temperature monitoring matters
Legionella bacteria multiply rapidly in water between 20°C and 45°C. At around 35-37°C (human body temperature), they thrive. Temperature control works by keeping water either:
- Too cold for bacteria to multiply effectively (below 20°C)
- Too hot for bacteria to survive (above 60°C storage, above 50°C distribution)
Temperature monitoring tells you whether your control measures are working. It's your early warning system. If temperatures drift into the danger zone, you know you have a problem before bacteria populations explode.
Temperature monitoring isn't just a bureaucratic box-ticking exercise. It's how you verify that your primary legionella defence is actually working. Without it, you're flying blind.
What the regulations say
The Control of Substances Hazardous to Health Regulations 2002 (COSHH) require you to:
- Prevent or control the risk of exposure to legionella
- Ensure control measures are used and maintained
- Monitor to ensure controls remain effective
The HSE's Approved Code of Practice L8 and technical guidance HSG274 specify that temperature control is a primary control measure, and that temperatures should be monitored and recorded regularly.
Monitoring frequency:
L8 and HSG274 recommend monthly temperature monitoring for most premises as a minimum. Higher-risk premises (healthcare, care homes, large buildings) may require weekly or even daily checks.
Critical temperature thresholds
These are the temperatures you're aiming for:
Hot water system temperatures
Storage (calorifiers, cylinders, tanks):
- Target: 60°C or higher throughout the stored water
- At this temperature, legionella bacteria are killed within minutes
- Most UK guidance specifies 60°C as the minimum
Distribution (pipes carrying hot water):
- Target: 50°C or higher throughout the system
- Hot water should reach outlets at 50°C or above within one minute of running the tap
Outlets (taps, showers):
- Target: At least 50°C after one minute of running
- This confirms that hot water distribution is effective
- Sentinel outlets (furthest or most vulnerable) are particularly important
Water at 60°C can cause scalding, particularly in vulnerable users. Thermostatic mixing valves (TMVs) can be fitted at outlets to blend hot and cold water to safe temperatures (typically 41-44°C) while maintaining high storage temperatures.
Cold water system temperatures
Storage (tanks, cisterns):
- Target: Below 20°C
- Cold water stored above 20°C allows legionella growth
- Insulation should keep heat out, not in
Distribution (pipes carrying cold water):
- Target: Below 20°C throughout the system
- Pipes should be insulated to prevent warming from surrounding air or proximity to hot pipes
Outlets (taps):
- Target: Below 20°C after running for 2 minutes
- If cold water reaches outlets above 20°C, you have a problem with your cold water system
The danger zone: 20-45°C
Water in this temperature range is where legionella thrives. If your monitoring reveals temperatures in this zone, you need immediate action. This is particularly problematic in:
- Poorly insulated cold water tanks in warm loft spaces
- Cold water pipes running alongside hot pipes
- Blended water systems with TMVs
- Little-used outlets where water sits stagnant
- Systems during summer months when ambient temperatures rise
Hot Water vs Cold Water Temperature Control
Hot Water Systems
- •Store at 60°C or higher
- •Distribute at 50°C or higher
- •Deliver at outlets at 50°C+ (within 1 minute)
- •Kill legionella through heat
- •Monitor: flow and return on calorifier, sentinel outlets
- •Risk: TMVs can create lukewarm water in pipework
Cold Water Systems
- •Store below 20°C
- •Distribute below 20°C
- •Deliver at outlets below 20°C (after 2 minutes)
- •Prevent legionella growth through cold
- •Monitor: storage tanks, sentinel outlets
- •Risk: warming from environment or proximity to hot pipes
Bottom line: Both hot and cold systems must be monitored. A hot water failure means bacteria aren't being killed. A cold water failure means bacteria can multiply. Both create risk.
What to monitor
You can't check every tap and pipe in your building every month. Instead, you monitor representative points that give you confidence in the overall system.
Hot water system monitoring points
1. Calorifiers and hot water cylinders
- Flow temperature: Hot water leaving the calorifier (should be 60°C+)
- Return temperature: Hot water returning to the calorifier after circulation (should be at least 50°C, ideally 55°C+)
- If the return temperature is too low, it suggests heat is being lost in distribution or circulation isn't adequate
2. Sentinel outlets
These are the outlets most vulnerable to legionella risk:
- Furthest outlet: The tap or shower furthest from the hot water source (longest pipe run, most heat loss)
- Least-used outlet: Outlets that are used infrequently (guest bathrooms, vacant rooms)
- Most vulnerable: Outlets serving vulnerable users (care home resident rooms, immunocompromised patient areas)
At sentinel outlets, measure:
- Hot water temperature after running for one minute
- Cold water temperature after running for two minutes
3. TMV outlets (if fitted)
- Measure the blended water temperature
- Separately measure the hot and cold feed temperatures before the valve
- TMVs can create lukewarm water, which may sit in pipework at ideal legionella growth temperatures
Cold water system monitoring points
1. Storage tanks (cisterns)
- Measure the water temperature inside the tank (ideally using a pocket thermometer or probe thermometer, not just surface temperature)
- Take readings in different parts of large tanks (top, middle, bottom) as temperature can stratify
2. Sentinel outlets
Same principle as hot water:
- Furthest outlet from the storage tank
- Least-used outlet
- Outlets in the warmest parts of the building
Measure cold water temperature after running for two minutes to get water that has traveled from the tank, not just water sitting in the outlet.
How many sentinel outlets?
This depends on the complexity of your system:
- Simple small building: 2-4 sentinel outlets may be sufficient
- Large building with multiple floors/wings: At least one sentinel outlet per zone or floor
- Complex system: Your risk assessment should identify specific monitoring points
Your legionella risk assessment should identify the specific monitoring points for your premises. Don't just randomly pick taps. Choose sentinels that represent the most vulnerable parts of your system.
Monthly monitoring requirements
For most premises, monthly temperature monitoring is the baseline. Here's what a monthly monitoring cycle should include:
Hot water checks (monthly)
- Calorifier flow temperature: 60°C or higher
- Calorifier return temperature: 50°C minimum (55°C+ preferred)
- Sentinel outlet temperatures: 50°C or higher after one minute
Cold water checks (monthly)
- Storage tank temperature: Below 20°C
- Sentinel outlet temperatures: Below 20°C after two minutes
TMV checks (monthly, if fitted)
- Blended water temperature: Check it's at the designed temperature (usually 41-44°C)
- Hot and cold feeds to TMV: Confirm hot is 50°C+ and cold is below 20°C
What else should be monitored?
In addition to temperatures, monthly checks often include:
- Visual inspection of tanks (lids secure, no contamination, no light ingress)
- Checking insulation is intact on pipes and tanks
- Flushing little-used outlets
- Checking water flow rates (poor flow can indicate problems)
- Checking for leaks, corrosion, or scale buildup
Temperature Monitoring Schedule
Run rarely-used taps and showers for 2 minutes to prevent stagnation
Check calorifier flow/return, sentinel hot and cold outlets, TMVs
Inspect tanks, check insulation, look for leaks or corrosion
Analyze logbooks for patterns, deteriorating performance, seasonal variations
Clean cold water storage tanks, descale calorifiers if needed
Update legionella risk assessment, revise monitoring points if needed
How to take readings correctly
Temperature monitoring is only useful if you do it properly. Here's how to get accurate, meaningful readings:
Equipment you'll need
1. Thermometer
- Digital probe thermometer: Most versatile, suitable for tanks and outlets (recommended)
- Infrared thermometer: Quick surface readings, but less accurate for water temperature
- Pocket dial thermometer: Simple and robust, good for tank readings
Calibration: Your thermometer should be calibrated regularly (at least annually) to ensure accuracy. Keep records of calibration.
2. Personal protective equipment (PPE)
- Heat-resistant gloves: Water at 60°C can cause severe burns
- Safety glasses: Protect against splashes when checking hot systems
- Consider face protection when working near hot calorifiers
3. Recording equipment
- Pre-printed logbook or temperature monitoring sheets
- Clipboard
- Pen (not pencil - records should be permanent)
Taking readings at outlets (taps and showers)
For hot water:
- Run the tap or shower at full hot (no cold water blended)
- Let it run for one minute by the clock
- Fill a container or hold the probe in the water stream
- Take the temperature reading
- Record the temperature, date, time, location, and your initials
For cold water:
- Run the tap at full cold
- Let it run for two minutes by the clock (to ensure you're getting water from the tank, not just pipe water)
- Take the temperature reading
- Record the result
Why these timings?
- One minute for hot water ensures you're measuring distributed water, not just the small amount sitting in the pipework near the outlet
- Two minutes for cold water ensures you're drawing water that has traveled from the storage tank
Taking readings at calorifiers
Flow temperature:
- Locate the flow thermometer or temperature gauge on the calorifier outlet pipe
- If using a surface probe, ensure good contact with the pipe (dry the pipe first)
- Wait 10-15 seconds for the reading to stabilize
- Record the temperature
Return temperature:
- Locate the return thermometer on the return pipe to the calorifier
- Same process as flow temperature
- The return should be at least 50°C, ideally 55°C+
Many modern calorifiers have built-in thermometers or digital displays. Use these, but verify them periodically with your own calibrated thermometer.
Taking readings at storage tanks
For cold water tanks:
- Remove the lid (check it's secure and fitted correctly first)
- Use a probe thermometer to measure water temperature
- Take readings in different parts of large tanks (temperatures can vary)
- Don't just measure surface temperature - measure at depth
- Replace the lid securely
Safety note: Cold water tanks can be in awkward locations (lofts, basements). Ensure safe access, adequate lighting, and don't work alone if access is difficult.
Common mistakes to avoid
Mistake 1: Not running water long enough
- Taking hot water readings immediately means you're measuring water sitting in the pipe, not system temperature
- Solution: Always wait the full minute for hot, two minutes for cold
Mistake 2: Using an uncalibrated thermometer
- Inaccurate readings give false confidence or trigger unnecessary alarms
- Solution: Calibrate annually, check against known temperature points periodically
Mistake 3: Taking readings at inconsistent locations
- One month you check the staff toilet, next month a different outlet
- Solution: Use the same sentinel outlets each month so you can spot trends
Mistake 4: Measuring blended water when you should measure hot
- If the cold tap is slightly open or a TMV is active, you're not measuring true hot water temperature
- Solution: Ensure only hot water is running during hot checks
Mistake 5: Not recording immediately
- Relying on memory leads to errors and lost data
- Solution: Record the reading on the spot before moving to the next location
If you're checking multiple outlets, work systematically. Start at the calorifier, then work through hot water sentinels, then cold water sentinels. This routine reduces the risk of missing a location.
Record keeping requirements
Temperature monitoring is only useful if you keep proper records. These records:
- Demonstrate ongoing compliance with L8 and COSHH
- Help you spot deteriorating performance or seasonal variations
- Provide evidence in case of an investigation or prosecution
- Show trends over time that might indicate developing problems
What to record
Every temperature reading should be documented with:
1. Basic information:
- Date and time of reading
- Location (specific tap, shower, or equipment)
- Temperature reading (in °C)
- Name or initials of person taking reading
2. Additional useful information:
- Weather/ambient temperature (can affect cold water tanks)
- Any observations (water discolored, low flow, unusual odor)
- Any remedial actions taken
- Follow-up required
Record formats
Paper logbooks:
- Pre-printed sheets with monitoring locations listed
- Simple to use, no technology required
- Should be kept in a dedicated folder or binder
- Use permanent ink, not pencil
Digital records:
- Spreadsheets, databases, or specialist software
- Easier to analyze trends and generate reports
- Should be backed up regularly
- Some systems allow thermometers to upload readings directly
Photographs:
- Some premises photograph calorifier gauges as supporting evidence
- Not a replacement for written records, but useful supplementary documentation
How long to keep records
Minimum: 5 years
The HSE recommends keeping legionella control records for at least five years. This aligns with general health and safety record-keeping requirements.
Better: Keep indefinitely
Many organizations keep water safety records indefinitely because:
- Legionnaires' disease has an incubation period of 2-10 days, but cases can be linked to exposures months or years earlier during investigations
- Long-term trend data is valuable for understanding system performance
- In the event of a prosecution, older records may be relevant
Storage:
- Keep records secure, dry, and organized
- Ensure records are accessible to those who need them (responsible person, auditors, inspectors)
- Back up digital records
- Consider keeping copies off-site in case of fire or flood
Falsifying or backdating temperature records is fraud. During investigations, inspectors can often spot fabricated records through inconsistent handwriting, patterns in readings, or physical evidence from the systems. Always record accurately.
What to do if temperatures are out of range
Finding an out-of-range temperature is not a failure - it's the monitoring system working. Now you need to respond appropriately.
Hot water too low
If hot water at outlets is below 50°C:
Immediate actions:
- Recheck the reading to confirm it's accurate
- Check other hot water outlets - is it localized or system-wide?
- Check calorifier temperature - is it at 60°C?
- Record the findings
Investigation:
- Is the calorifier thermostat set correctly?
- Is the calorifier heating element working?
- Are circulation pumps operating?
- Is there an issue with the specific outlet (TMV fault, pipe problem)?
- Has there been a change in demand or usage pattern?
Short-term actions:
- Increase calorifier temperature if it's too low
- Adjust boiler/heating controls
- Isolate and label the affected outlet if it serves vulnerable users
- Increase flushing frequency if it's a little-used outlet
Long-term solutions:
- Install trace heating on long pipe runs
- Improve insulation
- Upgrade undersized calorifier
- Remove dead-legs or rarely-used outlets
- Install a more powerful heating system
Cold water too warm
If cold water at outlets is above 20°C:
Immediate actions:
- Recheck the reading to confirm
- Check if it's localized (one outlet) or system-wide
- Check the cold water storage tank temperature
- Record findings
Investigation:
- Is the tank insulated properly? (It shouldn't be - insulation keeps heat in)
- Is the tank exposed to heat sources (hot pipes nearby, warm loft space)?
- Are cold pipes running alongside hot pipes?
- Is it summer and the ambient temperature is particularly high?
- Is the cold water being stored for too long (oversized tank)?
Short-term actions:
- Increase flushing frequency to bring fresh, cooler water through
- Investigate and rectify any immediate causes (leaking hot pipe warming the area)
Long-term solutions:
- Relocate cold water tank to a cooler location
- Install cold water tank in an air-conditioned plant room
- Insulate cold pipes to keep heat out (different from insulating to keep heat in)
- Separate hot and cold pipe runs
- Reduce tank size to increase turnover
- Install a chilled water system (rare, used in some specialist premises)
Calorifier return temperature too low
If return temperature is below 50°C:
This suggests heat is being lost in the distribution system, or circulation isn't adequate.
Investigation:
- Is the circulation pump working?
- Are all circuits circulating properly?
- Is insulation damaged or missing on return pipes?
- Are there dead-legs causing heat loss?
Actions:
- Check and repair/replace circulation pump
- Check insulation throughout system
- Balance the system to ensure even circulation
- Remove dead-legs where practical
Seasonal variations
Summer:
- Cold water temperatures may rise due to higher ambient temperatures
- Tanks in lofts can be particularly affected
- You may need more frequent flushing or temporary measures
Winter:
- Cold water temperatures naturally fall, often well below 20°C
- Hot water systems may struggle to maintain temperature in very cold weather
- Frozen pipes can cause system disruptions
Record seasonal trends:
Note seasonal variations in your records. This helps you:
- Anticipate problems each year
- Plan seasonal adjustments (increasing calorifier temperature in winter, more frequent flushing in summer)
- Distinguish between seasonal variations and genuine system failures
Care home legionella outbreak from inadequate temperature control
A care home in the Midlands experienced multiple cases of legionnaires' disease among residents. Investigation revealed that hot water temperatures had been reduced following resident complaints about scalding risk, and cold water tanks in the loft had no insulation, causing them to warm up during summer.
- ✗Hot water calorifier temperature reduced from 60°C to 50°C without risk assessment
- ✗No TMVs fitted to control outlet temperature while maintaining storage temperature
- ✗Cold water tank insulation removed during roof repairs and never replaced
- ✗Temperature monitoring was sporadic and readings were not acted upon
- ✗Loft space temperatures reached 35°C in summer, warming the cold water tank
- ✗Little-used outlets in vacant rooms were not flushed regularly
The care home was prosecuted and fined £180,000 plus costs. The registered manager was issued a personal fine. The CQC imposed conditions on the registration requiring independent water safety audits. Several residents required hospitalization, and one elderly resident died.
Temperature control is non-negotiable. If you need to protect vulnerable users from scalding, install TMVs at outlets, not by reducing storage temperatures. Regular monitoring only helps if you act on the findings.
Remedial actions and escalation
When you find a temperature problem, your response should be proportionate to the risk:
Low-risk findings
Example: One sentinel outlet is slightly out of range on one occasion, but other readings are normal.
Response:
- Re-test the same outlet next day or week
- If problem persists, investigate that specific outlet
- Continue routine monitoring
Medium-risk findings
Example: Multiple outlets showing temperatures in the 20-45°C range, or calorifier return temperature consistently low.
Response:
- Immediate investigation by competent person
- More frequent monitoring until resolved
- Implement interim controls (increased flushing, usage restrictions)
- Fix within a defined timeframe (days to weeks depending on circumstances)
High-risk findings
Example: System-wide temperature failures, cold water consistently above 25°C, hot water storage below 55°C, presence of vulnerable users.
Response:
- Immediate action required
- Consider restricting use of affected outlets
- Call in specialist contractor if internal expertise is insufficient
- Increase monitoring frequency (daily or more often)
- Notify responsible person and senior management
- Consider water sampling to assess bacterial contamination
- Document all actions taken
When to call in external help
You should consult a water treatment specialist or legionella control expert if:
- Temperature problems persist despite your remedial efforts
- You don't understand the cause of the problem
- Remedial work requires specialist skills (calorifier repair, system redesign)
- You have a vulnerable user population
- Water sampling shows high levels of legionella
- You've had a suspected case of legionnaires' disease linked to your premises
Don't wait for a crisis. If your monthly monitoring consistently shows borderline or out-of-range temperatures, act before it becomes an emergency. Persistent problems won't fix themselves.
Special considerations for different premises
Landlords and residential properties
Simple domestic properties:
- Monthly checks are often impractical for landlords of simple single-let houses
- Annual checks may be appropriate, combined with inspection during routine maintenance
- Provide tenants with guidance on running taps after holidays
HMOs and multi-occupancy:
- Monthly monitoring of communal hot and cold systems
- Check water temperatures in void rooms or rooms with vulnerable tenants
- Keep records accessible to managing agents and inspectors
Care homes and healthcare settings
Enhanced requirements:
- Weekly temperature monitoring (not just monthly)
- More sentinel outlets (at least one per floor or ward)
- Priority for monitoring near immunocompromised or elderly residents
- Immediate action on any out-of-range reading
- Regular audits by water safety group or responsible person
Hotels and guest accommodation
Focus on infrequently used rooms:
- Vacant rooms create stagnation risk
- Temperature check should follow vacancies
- Flushing regime before guest check-in
- Monitor after periods of low occupancy (off-season)
Offices and commercial premises
Lower intensity, but still essential:
- Monthly monitoring is usually sufficient
- Focus on bathrooms, kitchens, showers (if present)
- Monitoring after building closures (holidays, lockdowns)
- Consider seasonal variations in office temperature
Leisure facilities with spa pools
Spa pools require different approach:
- Spa water is typically 30-40°C (ideal for legionella)
- Temperature monitoring daily or more frequently
- Chemical disinfection (chlorine/bromine) is primary control, not temperature
- Regular water quality testing (chemical levels, pH, bacterial counts)
UK guidance: HSG274
The HSE's technical guidance HSG274 provides detailed advice on legionella control. It's published in three parts:
HSG274 Part 2: Hot and Cold Water Systems
Relevant sections on temperature monitoring:
- Section 2.53-2.62: Temperature control
- Section 2.82-2.88: Monitoring and inspection
- Appendix 2: Operational monitoring and inspection checklist
Key recommendations:
- Monthly monitoring of temperatures at sentinel outlets
- More frequent checks (weekly or continuous) for higher-risk premises
- Calorifier flow should be 60°C, return at least 50°C
- Hot water at outlets should reach 50°C within one minute
- Cold water should be below 20°C
HSG274 Part 3: Other Risk Systems
Covers cooling towers, spa pools, and other specialized systems. Temperature monitoring requirements vary by system type.
HSG274 and L8 relationship
- L8 (ACOP): Approved Code of Practice, has special legal status
- HSG274: Technical guidance, provides practical detail on implementing L8
- Both are published by HSE and should be used together
You can download HSG274 parts 1, 2, and 3 from the HSE website. While L8 is sold as a priced publication, HSG274 is available as free PDF downloads. Both are essential reading for anyone responsible for water safety.
Continuous monitoring systems
Some premises use automated continuous temperature monitoring:
How they work
- Temperature sensors fitted at key points (calorifier flow/return, sentinel outlets)
- Sensors connected to a data logging system or building management system (BMS)
- System records temperatures continuously (e.g., every 15 minutes)
- Alarms trigger if temperatures go out of range
Advantages
- Early detection of problems (hours, not weeks)
- Comprehensive data for trend analysis
- Reduces manual monitoring workload
- Provides evidence of continuous compliance
Disadvantages
- Higher initial cost
- Requires maintenance and calibration
- Can generate false alarms
- Doesn't replace the need for physical checks and system inspections
When continuous monitoring makes sense
- Large or complex buildings with extensive water systems
- High-risk premises (hospitals, care homes)
- Buildings where manual monitoring is difficult or dangerous
- Premises with history of temperature control problems
Continuous monitoring is a supplement to, not a replacement for, your regular inspection and maintenance program.
Training and competence
The person conducting temperature monitoring should be competent, meaning they:
- Understand why temperature control matters for legionella control
- Know what temperatures to look for
- Can take accurate readings using appropriate equipment
- Know how to record results properly
- Understand when to escalate concerns
- Can work safely around hot water and in tank spaces
Training options
In-house training:
- Suitable for simple systems
- Senior staff or responsible person can train operational staff
- Document the training (date, content, attendees)
External training:
- City & Guilds legionella awareness or control courses
- Legionella Control Association (LCA) training
- Water treatment company training sessions
- One-day legionella awareness courses widely available
Refresher training:
- Every 2-3 years, or when procedures change
- When new staff take on water safety duties
- After incidents or near-misses
Competence isn't just about qualifications. Someone with years of experience maintaining your specific water systems may be more competent than someone with a certificate but no practical experience. Use your judgment.
Frequently asked questions
Infrared thermometers measure surface temperature, not water temperature. They're useful for quick checks of pipe surfaces, but not suitable for accurate outlet temperature readings. Use a probe or pocket thermometer that can be placed directly in the water stream or immersed in tanks.
This is a common problem in the UK during hot weather. Short-term solutions include increasing flushing frequency and reducing storage time. Long-term, consider relocating tanks to cooler locations, installing cooled plant rooms, or improving ventilation around tanks. In extreme cases, you may need to consult a water treatment specialist about chilled water systems.
Yes. Regular monitoring demonstrates ongoing compliance. Water systems can deteriorate gradually (insulation damage, pump failure, scale buildup) and you won't know unless you monitor consistently. Monthly checks are the minimum for most premises under HSG274 guidance.
Yes, but also measure the hot and cold water feeding the TMV separately. The blended water from a TMV should be at the designed temperature (usually 41-44°C to prevent scalding), but you need to confirm that the hot feed is at least 50°C and cold is below 20°C. If the hot feed is too cool, the TMV won't help with legionella control.
No, the return temperature should be at least 50°C, with 55°C+ being best practice. A return temperature of 48°C suggests heat is being lost in distribution or your circulation pump isn't maintaining adequate flow. Investigate and resolve - this is creating water in the distribution system at a temperature where legionella can survive.
Your thermometer should be accurate to within ±1°C at the temperatures you're measuring. Most digital probe thermometers meet this standard. Calibrate your thermometer at least annually, and check it periodically against a known accurate reference (e.g., boiling water at 100°C, ice water at 0°C).
Yes, various systems exist that allow remote monitoring via smartphone apps or web interfaces. These can be useful for convenience and early alerts, but ensure the system is calibrated, reliable, and doesn't replace physical inspections. Manual checks are still important to verify system operation and catch issues the sensors might miss.
Rarely-used outlets are often the highest risk because water sits stagnant. If a little-used outlet is out of range, you have several options: flush it weekly to maintain safe temperatures, consider removing it permanently (cap off the pipe), or increase the temperature/flow in that branch of the system. Don't ignore it just because it's rarely used.
No. You monitor 'sentinel outlets' - representative locations that indicate the health of the system. Typically this includes the furthest outlets from the calorifier/tanks, the least-used outlets, and those serving vulnerable users. Your risk assessment should specify which outlets to monitor.
The minimum is 60°C throughout the stored water. Many systems store at 60-65°C to provide a margin for error. Very high temperatures (above 65°C) can increase scale formation and energy costs. 60°C is the recognized threshold for killing legionella - above this, you get diminishing returns and increased operating costs.
Temperature monitoring checklist
Use this checklist for your monthly monitoring:
Before you start:
- Calibrated thermometer available
- PPE ready (heat-resistant gloves, safety glasses)
- Logbook or recording sheets prepared
- Familiar with locations of calorifiers, tanks, and sentinel outlets
Hot water system:
- Calorifier flow temperature recorded (target: 60°C+)
- Calorifier return temperature recorded (target: 50°C+, ideally 55°C+)
- Sentinel outlet 1: Hot temperature after 1 minute (target: 50°C+)
- Sentinel outlet 2: Hot temperature after 1 minute (target: 50°C+)
- Sentinel outlet 3: Hot temperature after 1 minute (target: 50°C+)
- [Additional sentinels as identified in risk assessment]
Cold water system:
- Cold water storage tank temperature (target: below 20°C)
- Sentinel outlet 1: Cold temperature after 2 minutes (target: below 20°C)
- Sentinel outlet 2: Cold temperature after 2 minutes (target: below 20°C)
- Sentinel outlet 3: Cold temperature after 2 minutes (target: below 20°C)
- [Additional sentinels as identified in risk assessment]
TMVs (if fitted):
- TMV blended temperature at safe level (typically 41-44°C)
- Hot feed to TMV at 50°C+
- Cold feed to TMV below 20°C
Visual checks:
- Cold water tank lids secure and in place
- No visible contamination in tanks
- Insulation intact on hot pipes
- No leaks or corrosion visible
- No unusual odors or discoloration
Follow-up actions:
- Any out-of-range readings investigated
- Remedial actions documented
- Responsible person notified of any concerns
- Logbook completed and signed
Review:
- Trends analyzed (are any readings consistently borderline?)
- Seasonal patterns noted
- Equipment calibration up to date
- Next monitoring date scheduled
Next steps
Want to understand the bigger picture of legionella control?
Not sure if you need a formal risk assessment?
Do I need a legionella risk assessment? →
Concerned about your monitoring findings?
Struggling to maintain safe water temperatures? A water hygiene specialist can investigate your system, identify why temperatures are out of range, and recommend cost-effective solutions.
Related articles:
Useful tools: